8.1.6.3
ESXSWI Input signals
Table 259: ESXSWI Input signals
Name
Type
Default
Description
POSOPEN
BOOLEAN
0=False
Apparatus open posi-
tion
POSCLOSE
BOOLEAN
0=False
Apparatus close posi-
tion
ENA_OPEN
BOOLEAN
1=True
Enables opening
ENA_CLOSE
BOOLEAN
1=True
Enables closing
BLK_OPEN
BOOLEAN
0=False
Blocks opening
BLK_CLOSE
BOOLEAN
0=False
Blocks closing
AU_OPEN
BOOLEAN
0=False
Executes the com-
mand for open direc-
tion
1
2
AU_CLOSE
BOOLEAN
0=False
Executes the com-
mand for close direc-
tion
1
2
ITL_BYPASS
BOOLEAN
0=False
Discards ENA_OPEN
and ENA_CLOSE in-
terlocking when TRUE
8.1.6.4
DCXSWI Output signals
Table 260: DCXSWI Output signals
Name
Type
Description
SELECTED
BOOLEAN
Object selected
EXE_OP
BOOLEAN
Executes the command for
open direction
EXE_CL
BOOLEAN
Executes the command for
close direction
OPENPOS
BOOLEAN
Apparatus open position
CLOSEPOS
BOOLEAN
Apparatus closed position
OKPOS
BOOLEAN
Apparatus position is ok
OPEN_ENAD
BOOLEAN
Opening is enabled based on
the input status
CLOSE_ENAD
BOOLEAN
Closing is enabled based on
the input status
1
Not available for monitoring
2
Always direct operation
1MRS758407 C
Control functions
SMU615
Technical Manual
237
Summary of Contents for Relion SMU615