Table 7: Analog input settings, phase voltages
Parameter
Values (Range)
Unit
Step
Default
Description
Primary voltage
0.100 ... 440.000
kV
0.001
20.000
Primary rated volt-
age
Secondary voltage
60...210
V
1
100
Secondary rated
voltage
VT connection
1=Wye
2=Delta
2=Delta
Voltage transducer
measurement con-
nection
Amplitude Corr A
0.9000 ... 1.1000
0.0001
1.0000
Phase A Voltage
phasor magnitude
correction of an
external voltage
transformer
Amplitude Corr B
0.9000 ... 1.1000
0.0001
1.0000
Phase B Voltage
phasor magnitude
correction of an
external voltage
transformer
Amplitude Corr C
0.9000 ... 1.1000
0.0001
1.0000
Phase C Voltage
phasor magnitude
correction of an
external voltage
transformer
Division ratio
1000 ... 20000
1
10000
Voltage sensor divi-
sion ratio
Voltage input type
1=Voltage trafo
3=CVD sensor
1=Voltage trafo
Type of the voltage
input
Angle Corr A
-8.000 … 8.000 deg deg
0.0001
0.0000
Phase A Voltage
phasor angle cor-
rection of an exter-
nal voltage trans-
former
Angle Corr B
-8.000 … 8.000 deg deg
0.0001
0.0000
Phase B Voltage
phasor angle cor-
rection of an exter-
nal voltage trans-
former
Angle Corr C
-8.000 … 8.000 deg deg
0.0001
0.0000
Phase C Voltage
phasor angle cor-
rection of an exter-
nal voltage trans-
former
3.1.4
Authorization settings
Table 8: Authorization settings
Parameter
Values (Range)
Unit
Step
Default
Description
Remote Update
0=Disable
1=Enable
0=Disable
Remote update
Secure Communication
0=False
1=True
1=True
Secure Communication
Authority logging
1=None
2=Configuration change
5=Settings edit
6=All
1=None
Authority logging level
Table continues on the next page
Basic functions
1MRS758407 C
34
SMU615
Technical Manual