8.1.6.5
ESXSWI Output signals
Table 261: ESXSWI Output signals
Name
Type
Description
SELECTED
BOOLEAN
Object selected
EXE_OP
BOOLEAN
Executes the command for
open direction
EXE_CL
BOOLEAN
Executes the command for
close direction
OPENPOS
BOOLEAN
Apparatus open position
CLOSEPOS
BOOLEAN
Apparatus closed position
OKPOS
BOOLEAN
Apparatus position is ok
OPEN_ENAD
BOOLEAN
Opening is enabled based on
the input status
CLOSE_ENAD
BOOLEAN
Closing is enabled based on
the input status
8.1.7
Settings
8.1.7.1
CBXCBR Non group settings
Table 262: CBXCBR Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation mode
on/off
Select timeout
10000...300000
ms
10000
30000
Select timeout in
ms
Pulse length
10...60000
ms
1
200
Open and close
pulse length
Control model
0=status-only
1=direct-with-nor-
mal-security
4=sbo-with-en-
hanced-security
4=sbo-with-en-
hanced-security
Select control mod-
el
Operation timeout 10...60000
ms
1
500
Timeout for nega-
tive termination
Identification
CBXCBR1 switch
position
Control Object
identification
Table 263: CBXCBR Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation counter
0...10000
1
0
Breaker operation
cycles
Adaptive pulse
0=False
1=True
1=True
Stop in right posi-
tion
Table continues on the next page
Control functions
1MRS758407 C
238
SMU615
Technical Manual