Parameter
Values (Range)
Unit
Step
Default
Description
Directional Coef
-3.00...-0.50
0.01
-1.50
Directional coeffi-
cient for CB life cal-
culation
Initial CB Rmn life
0...99999
1
5000
Initial value for the
CB remaining life
Rated Op current
100.00...5000.00
A
0.01
1000.00
Rated operating
current of the
breaker
Rated fault current 500.00...75000.00
A
0.01
5000.00
Rated fault current
of the breaker
Op number rated
1...99999
1
10000
Number of opera-
tions possible at
rated current
Op number fault
1...10000
1
1000
Number of opera-
tions possible at
rated fault current
Inactive Alm days
0...9999
1
2000
Alarm limit value of
the inactive days
counter
Travel time Clc
mode
1=From Cmd to Pos
2=From Pos to Pos
2=From Pos to Pos Travel time calcu-
lation mode selec-
tion
Table 199: SSCBR Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Opening time Cor
-100...100
ms
1
10
Correction factor
for open travel time
in ms
Closing time Cor
-100...100
ms
1
10
Correction factor
for CB close travel
time in ms
Counter initial Val
0...99999
1
0
The operation num-
bers counter initial-
ization value
Ini Acc currents Pwr 0.00...20000.00
0.01
0.00
Initial value for ac-
cumulation energy
(Iyt)
Life alarm level
0...99999
1
500
Alarm level for CB
remaining life
Pressure alarm
time
0...60000
ms
1
10
Time delay for gas
pressure alarm in
ms
Pres lockout time
0...60000
ms
10
10
Time delay for gas
pressure lockout in
ms
Ini inactive days
0...9999
1
0
Initial value of the
inactive days coun-
ter
Inactive Alm hours
0...23
h
1
0
Alarm time of the
inactive days coun-
ter in hours
6.1.8
Monitored data
1MRS758407 C
Condition monitoring functions
SMU615
Technical Manual
179
Summary of Contents for Relion SMU615
Page 1: ... RELION Substation Merging Unit SMU615 Technical Manual ...
Page 2: ......