Technical revision
Change
Default value changed to 30 s for
Operation
timeout
setting.
C
Outputs
OPENPOS
and
CLOSEPOS
are forced
to “FALSE” in case status is Faulty (11).
Table 273: ESXSWI Technical revision history
Technical revision
Change
B
Maximum and default values changed to 60 s
and 10 s respectively for
Event delay
settings.
Default value changed to 30 s for
Operation
timeout
setting.
C
Outputs
OPENPOS
and
CLOSEPOS
are forced
to “FALSE” in case status is Faulty (11).
8.2
Disconnector position indication DCSXSWI and
Earthing switch indication ESSXSWI
8.2.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE
C37.2 device
number
Disconnector position indication DCSXSWI
I<->O DC
I<->O DC
Earthing switch indication
ESSXSWI
I<->O ES
I<->O ES
8.2.2
Function block
Figure 138: Function block
Figure 139: Function block
8.2.3
Functionality
The functions DCSXSWI and ESSXSWI indicate remotely and locally the open, close
and undefined states of the disconnector and earthing switch. The functionality
Control functions
1MRS758407 C
242
SMU615
Technical Manual