Parameter
Values (Range)
Unit
Step
Default
Description
Ng Seq A low low
Lim
0.00...40.00
xIn
1
0.00
Low alarm current
limit for negative
sequence current
Ng Seq A deadband 100...100000
1
2500
Deadband configu-
ration value for
negative sequence
current for inte-
gral calculation.
(percentage of dif-
ference between
min and max as
0,001 % s)
Zro A Hi high Lim
0.00...40.00
xIn
1
0.20
High alarm current
limit for zero se-
quence current
Zro A High limit
0.00...40.00
xIn
1
0.05
High warning cur-
rent limit for zero
sequence current
Zro A low limit
0.00...40.00
xIn
1
0.00
Low warning cur-
rent limit for zero
sequence current
Zro A low low Lim
0.00...40.00
xIn
1
0.00
Low alarm current
limit for zero se-
quence current
Zro A deadband
100...100000
1
2500
Deadband configu-
ration value for
zero sequence cur-
rent for integral cal-
culation. (percent-
age of difference
between min and
max as 0,001 % s)
7.1.8.5
Monitored data
CSMSQI Monitored data
Table 236: CSMSQI Monitored data
Name
Type
Values (Range)
Unit
Description
NgSeq-A
FLOAT32
0.00...40.00
xIn
Measured nega-
tive sequence
current
PsSeq-A
FLOAT32
0.00...40.00
xIn
Measured posi-
tive sequence
current
ZroSeq-A
FLOAT32
0.00...40.00
xIn
Measured zero
sequence current
I2_INST
FLOAT32
0.00...40.00
xIn
Negative se-
quence current
amplitude, in-
stantaneous val-
ue
I2_ANGL
FLOAT32
-180.00...180.00
deg
Negative se-
quence current
angle
Table continues on the next page
1MRS758407 C
Measurement functions
SMU615
Technical Manual
207