5.2.6.2
CCSPVC Output signals
Table 177: CCSPVC Output signals
Name
Type
Description
FAIL
BOOLEAN
Fail output
ALARM
BOOLEAN
Alarm output
5.2.7
Settings
5.2.7.1
CCSPVC Non group settings
Table 178: CCSPVC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation On / Off
Start value
0.05...0.20
xIn
0.01
0.05
Minimum operate
current differential
level
Table 179: CCSPVC Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Max operate cur-
rent
1.00...5.00
xIn
0.01
1.50
Block of the func-
tion at high phase
current
5.2.8
Monitored data
5.2.8.1
CCSPVC Monitored data
Table 180: CCSPVC Monitored data
Name
Type
Values (Range)
Unit
Description
IDIFF
FLOAT32
0.00...40.00
xIn
Differential cur-
rent
CCSPVC
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Supervision functions
1MRS758407 C
152
SMU615
Technical Manual