Name
Type
Values (Range)
Unit
Description
1=open
2=closed
3=faulty
8.2.8.2
ESSXSWI Monitored data
Table 284: ESSXSWI Monitored data
Name
Type
Values (Range)
Unit
Description
POSITION
Dbpos
0=intermediate
1=open
2=closed
3=faulty
Apparatus posi-
tion indication
8.2.9
Technical revision history
Table 285: DCSXSWI Technical revision history
Technical revision
Change
B
Maximum and default values changed to 60 s
and 30 s respectively for
Event delay
settings.
C
Outputs
OPENPOS
and
CLOSEPOS
are forced
to “FALSE” in case status is Faulty (11).
Table 286: ESSXSWI Technical revision history
Technical revision
Change
B
Maximum and default values changed to 60 s
and 30 s respectively for
Event delay
settings.
C
Outputs
OPENPOS
and
CLOSEPOS
are forced
to “FALSE” in case status is Faulty (11).