energizing check. The input
SYNC_ITL_BYP
can be used for bypassing this control.
The
SYNC_ITL_BYP
input can be used to activate
CLOSE_ENAD
discarding the
ENA_CLOSE
and
SYNC_OK
input states. However, the
BLK_CLOSE
input always blocks
the
CLOSE_ENAD
output.
The CB opening (
OPEN_ENAD
) logic is the same as CB closing logic, except
that
SYNC_OK
is used only in closing. The
SYNC_ITL_BYP
input is used in both
CLOSE_ENAD
and
OPEN_ENAD
logics.
Figure 132: Enabling and blocking logic for CLOSE_ENAD and OPEN_ENAD signals
Opening and closing operations
The opening and closing operations are available via communication, binary inputs
or commands. As a prerequisite for control commands, there are enabling and
blocking functionalities for both opening and closing commands (
CLOSE_ENAD
and
OPEN_ENAD
signals). If the control command is executed against the blocking or
if the enabling of the corresponding command is not valid, CBXCBR, DCXSWI and
ESXSWI generate an error message.
When close command is given from communication by activating the
AU_CLOSE
input, it is carried out (the
EXE_CL
output) only if
CLOSE_ENAD
is TRUE.
If the SECRSYN function is used in “Command” mode, the
CL_REQ
output can be
used in CBXCBR. Initially, the
SYNC_OK
input is FALSE. When the close command
given, it activates the
CL_REQ
output, which should be routed to SECRSYN. The
close command is then processed only after
SYNC_OK
is received from SECRSYN.
When using SECRSYN in the “Command” mode, the CBXCBR setting
Operation timeout should be set longer than SECRSYN setting Maximum
Syn time.
1MRS758407 C
Control functions
SMU615
Technical Manual
231