Parameter
Values (Range)
Unit
Step
Default
Description
5=MM/DD/YYYY
6=YYYY-MM-DD
7=YYYY-DD-MM
8=YYYY/DD/MM
Table 25: Time settings
Parameter
Values (Range)
Unit
Step
Default
Description
Synch source
0=None
3=IEEE 1588
3=IEEE 1588
Time synchronization
source
PTP domain ID
0...255
1
0
The domain is identi-
fied by an integer, the
domainNumber, in the
range of 0 to 255.
PTP priority 1
1
0...255
1
128
PTP priority 1, in the
range of 0 to 255.
PTP priority 2
0...255
1
128
PTP priority 2, in the
range of 0 to 255.
PTP announce mode
1=Basic IEEE1588
2=Power Profile
1=Basic IEEE1588
PTP announce frame
mode
Table 26: Time settings
Parameter
Values (Range)
Unit
Step
Default
Description
Date
0
Date
Time
0
Time
Local time offset
-840...840
min
1
0
Local time offset in
minutes
Table 27: Time settings
Parameter
Values (Range)
Unit
Step
Default
Description
DST in use
0=False
1=True
1=True
DST in use setting
DST on time
(hours)
0...23
h
2
Daylight saving
time on, time (hh)
DST on time (mi-
nutes)
0...59
min
0
Daylight saving
time on, time (mm)
DST on date (day)
1...31
1
Daylight saving
time on, date
(dd:mm)
DST on date
(month)
1=January
2=February
3=March
4=April
5=May
6=June
7=July
8=August
5=May
Daylight saving
time on, date
(dd:mm)
Table continues on the next page
1
Smaller value has higher priority
1MRS758407 C
Basic functions
SMU615
Technical Manual
53