![ABB Relion SMU615 Technical Manual Download Page 108](http://html.mh-extra.com/html/abb/relion-smu615/relion-smu615_technical-manual_3045381108.webp)
3.13.6.1
Function block
Figure 71: Function block
3.13.6.2
Functionality
The set-reset (8 pcs) function SRGAPC is a simple SR flip-flop with a memory that
can be set or that can reset an output from the
S#
or
R#
inputs, respectively.
The function contains eight independent set-reset flip-flop latches where the
SET
input has the higher priority over the
RESET
input. The status of each
Q#
output
is retained in the nonvolatile memory. The individual reset for each
Q#
output is
available on the WHMI or through tool via communication.
Table 139: Truth table for SRGAPC
S#
R#
Q#
0
0
0
1
0
1
0
1
0
1
1
1
1
3.13.6.3
Signals
Table 140: SRGAPC Input signals
Name
Type
Default
Description
S1
BOOLEAN
0=False
Set Q1 output when
set
R1
BOOLEAN
0=False
Resets Q1 output
when set
Table continues on the next page
1
Keep state/no change
Basic functions
1MRS758407 C
108
SMU615
Technical Manual
Summary of Contents for Relion SMU615