Parameter
Values (Range)
Unit
Step
Default
Description
5=off
Num of phases
1=1 out of 3
2=2 out of 3
3=3 out of 3
1=1 out of 3
Number of phases
required by limit
supervision
V high high limit
0.00...4.00
xUn
1
1.40
High alarm voltage
limit
V high limit
0.00...4.00
xUn
1
1.20
High warning volt-
age limit
V low limit
0.00...4.00
xUn
1
0.00
Low warning volt-
age limit
V low low limit
0.00...4.00
xUn
1
0.00
Low alarm voltage
limit
V deadband
100...100000
1
10000
Deadband configu-
ration value for in-
tegral calculation.
(percentage of dif-
ference between
min and max as
0,001 % s)
Table 217: VMMXU Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Measurement
mode
1=RMS
2=DFT
2=DFT
Selects used meas-
urement mode
7.1.5.5
Monitored data
VMMXU Monitored data
Table 218: VMMXU Monitored data
Name
Type
Values (Range)
Unit
Description
U12-kV
FLOAT32
0.00...4.00
xUn
Measured phase
to phase voltage
amplitude phase
AB
U23-kV
FLOAT32
0.00...4.00
xUn
Measured phase
to phase voltage
amplitude phase
BC
U31-kV
FLOAT32
0.00...4.00
xUn
Measured phase
to phase voltage
amplitude phase
CA
BLOCK
BOOLEAN
0=False
1=True
Block signal for
all binary out-
puts
HIGH_ALARM
BOOLEAN
0=False
1=True
High alarm
Table continues on the next page
1MRS758407 C
Measurement functions
SMU615
Technical Manual
197