Description
Type test value
Reference
Power frequency magnetic
field immunity test
• Continuous
• 1...3 s
300 A/m
1000 A/m
IEC 60255-26:2013
IEC 61000-4-8:2009
GB 14598.26-2015
Pulse magnetic field immuni-
ty test
1000 A/m
6.4/16 µs
IEC 61000-4-9:2001
GB 14598.26-2015
Damped oscillatory magnetic
field immunity test
• 2 s
• 1 MHz
100 A/m
400 transients/s
IEC 61000-4-10:2001
GB 14598.26-2015
A.C. and D.C. voltage dips and
interruptions test
30%/10 ms
60%/100 ms
60%/1000 ms
>95%/5000 ms
IEC 60255-26:2013
IEC 61000-4-11:2004
IEC 61000-4-29:2000
GB 14598.26-2015
Power frequency immunity
test
• Common mode
• Differential mode
Binary inputs only
300 V rms
150 V rms
IEC 60255-26:2013
IEC 61000-4-16:1998+A2:2009
GB 14598.26-2015
Emission tests
• Conducted
0.15...0.50 MHz
0.5...30 MHz
• Radiated
30...230 MHz
230...1000 MHz
1…3 GHz
3…6 GHz
<79 dB (µV) quasi peak
<66 dB (µV) average
<73 dB (µV) quasi peak
<60 dB (µV) average
<40 dB (µV/m) quasi peak,
measured at 10m distance
<47 dB (µV/m) quasi peak,
measured at 10m distance
<76 dB (µV/m) peak
<56 dB (µV/m) average,
measured at 3m distance
<80 dB (µV/m) peak
<60 dB (µV/m) average,
measured at 3m distance
IEC 60255-26
:
2013
CISPR 11:2009+A1:2010
CISPR 22
:
2008
GB 14598.26-2015
12.2
Insulation tests
Table 307: Insulation tests
Description
Type test value
Reference
Dielectric tests
2 kV, 50 Hz, 1 min
IEC 60255-272013
Table continues on the next page
1MRS758407 C
Merging unit and functionality tests
SMU615
Technical Manual
265