F_TRIG Output signal
Table 97: F_TRIG Output signal
Name
Type
Description
Q
BOOLEAN
Output signal
Settings
The function does not have any parameters available in PCM600.
3.13.1.9
T_POS_XX function blocks
Function block
Figure 54: Function blocks
Functionality
The circuit breaker position information can be communicated with the IEC 61850
GOOSE messages. The position information is a double binary data type which is
fed to the
POS
input.
T_POS_CL and T_POS_OP are used for extracting the circuit breaker status
information. Respectively, T_POS_OK is used to validate the intermediate or faulty
breaker position.
Table 98: Cross reference between circuit breaker position and the output of the
function block
Circuit breaker
position
Output of the function block
T_POS_CL
T_POS_OP
T_POS_OK
Intermediate '00'
FALSE
FALSE
FALSE
Close '01'
TRUE
FALSE
TRUE
Open '10'
FALSE
TRUE
TRUE
Faulty '11'
TRUE
TRUE
FALSE
Signals
T_POS_CL Input signals
Table 99: T_POS_CL Input signals
Name
Type
Default
Description
POS
Double binary
0
Input signal
1MRS758407 C
Basic functions
SMU615
Technical Manual
93