Fault indication
Fault
code
Additional
information
Fast self-
recovery
attempt
(# of
attempts)
Slow 10
min self-
recovery (#
of
attempts)
Immediate
permanen
t IRF-
mode
Action in permanent fault state
relay normal operation. If not recov-
er by restarting, exchange the com-
munication module including ARC
inputs in slot X000.
Internal Fault Conf.
error,X000
62
Start up error:
Card in slot X000
is wrong type, is
missing, does not
belong to original
configuration or
card firmware is
faulty.
No
No
Yes
"Check that the communication
card in slot X000 is proper type and
properly installed. Check that the
plug-in unit is properly installed and
plug-in unit handle is properly fixed
to closed position. Then restart
the relay. If does not recover by re-
starting, it is hardware module fail-
ure most likely. Exchange the com-
munication module in slot X000.
In some rare cases also communi-
cation storm may cause this. De-
tach the ethernet communication
cable(s) from the communication
module and reboot the relay. If
not recover,exchange the communi-
cation module in slot X000. "
Internal Fault Conf.
error,X100
63
Start up error:
Card in slot X100
is wrong type, is
missing, does not
belong to original
configuration or
card firmware is
faulty.
No
No
Yes
"Check that the card in slot X100
is proper type and properly instal-
led. Check that the plug-in unit is
properly installed and plug-in unit
handle is properly fixed to closed
position. Then restart the relay. If
does not recover by restarting, it is
hardware module failure most likely.
Exchange the hardware module in
slot X100."
Internal Fault Conf.
error,X110
64
Start up error:
Card in slot X110
is wrong type, is
missing, does not
belong to original
configuration or
card firmware is
faulty.
No
No
Yes
"Check that the card in slot X110
is proper type and properly instal-
led. Check that the plug-in unit is
properly installed and plug-in unit
handle is properly fixed to closed
position. Then restart the relay. If
does not recover by restarting, it is
hardware module failure most likely.
Exchange the hardware module in
slot X110."
Internal Fault Conf.
error,X120
65
Start up error:
Card in slot X120
is wrong type, is
missing, does not
belong to original
configuration or
card firmware is
faulty.
No
No
Yes
"Check that the card in slot X120
is proper type and properly instal-
led. Check that the plug-in unit is
properly installed and plug-in unit
handle is properly fixed to closed
position. Then restart the relay. If
does not recover by restarting, it is
hardware module failure most likely.
Exchange the hardware module in
slot X120."
Internal Fault Conf.
error,X130
66
Start up error:
Card in slot X130
is wrong type, is
missing, does not
belong to original
configuration or
card firmware is
faulty.
No
No
Yes
"Check that the card in slot X130
is proper type and properly instal-
led. Check that the plug-in unit is
properly installed and plug-in unit
handle is properly fixed to closed
position. Then restart the relay. If
does not recover by restarting, it is
hardware module failure most likely.
Exchange the hardware module in
slot X130."
Internal Fault Card
error,X000
72
Card in slot X000
is faulty.
Yes (2)
Yes (3)
No
"Check the plug-in unit connector
pins in the card by detaching the
plug-in unit. If pins are OK, ex-
change the communication module
in slot X000. In some rare cases al-
so communication storm may cause
Table continues on the next page
1MRS758407 C
Basic functions
SMU615
Technical Manual
41