Table 41:
Line specifications for three transmission line sections
Parameter
Line section 1
Line section 2
Line section 3
LineLength(km)
4.8
40.3
18.2
RL Positive sequence
resistance (Ohm/Ph.)
RL1 = 0.575
RL2= 11.122
RL3= 5.609
XL Positive sequence
reactance (Ohm/Ph.)
XL1 = 1.206
XL2= 10.034
XL3= 4.765
R0 Zero sequence
resistance (Ohm/Ph.)
R01 = 0.543
R02 = 8.293
R03 = 3.752
X0 Zero sequence
reactance (Ohm/Ph.)
X01 = 1.284
X02 = 12.429
X03 = 6.858
Setting related to line section 1
1
*
2
1
01
1
RL
RL
R
REOverRL
IECEQUATION15082 V1 EN-US
(Equation 79)
REOverRL1
= The positive sequence resistance.
REOverRL1
should be set as
-0.02783.
1
*
2
1
01
1
XL
XL
X
XEOverXL
IECEQUATION15083 V1 EN-US
(Equation 80)
XEOverXL1
= The positive sequence reactance.
REOverRL1
should be set as
0.0323.
Setting related to line section 2
2
*
2
2
02
2
RL
RL
R
REOverRL
IECEQUATION15112 V1 EN-US
(Equation 81)
REOverRL2
= The positive sequence resistance.
REOverRL2
should be set as
-0.1272.
2
*
2
2
02
2
XL
XL
X
XEOverXL
IECEQUATION15113 V1 EN-US
(Equation 82)
XEOverXL2
= The positive sequence reactance.
REOverRL2
should be set as
0.1193.
Setting related to line section 3
3
*
2
3
03
3
RL
RL
R
REOverRL
IECEQUATION15114 V1 EN-US
(Equation 83)
REOverRL3
= The positive sequence resistance.
REOverRL3
should be set as
-0.16554.
1MRK 506 375-UEN A
Section 15
Monitoring
Railway application RER670 2.2 IEC
409
Application manual
Summary of Contents for RELION RER670
Page 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 48: ...42 ...
Page 70: ...64 ...
Page 80: ...74 ...
Page 100: ...94 ...
Page 210: ...204 ...
Page 364: ...358 ...
Page 384: ...378 ...
Page 468: ...462 ...
Page 494: ...488 ...
Page 504: ...498 ...
Page 505: ...499 ...