tI0
: Delay time for the residual overcurrent start. Residual overcurrent start is
delayed by settable time delay tI0. The default setting is 0.2s.
If magnitude of the phase L1 current is more than KI times magnitude of phase L2
current together with delayed residual overcurrent start signal and
ModePhSelKI
is
set to
Off
, the L1E loop will be released for distance measuring. This is valid for
phase L2 as well.
Phase selection based on residual overcurrent start is done only if the stub mode is
not selected. This means that the setting
ModeStubline
is set to
Off
and there are no
outputs from the underimpedance starting loops.
I01
: This setting is used to detect the high short circuit current during the blocking
time
tI01
when starting element impedance loop has picked up. A default setting of
300%
IB
is used.
tI01
: This is used as the blocking time of distance measuring for the transient earth
fault. A default setting of 0.1s is used.
The underimpedance start and residual overcurrent start operates in the event of an
earth fault. Once the earth fault is detected, it is blocked for a set time delay
tI01
to
avoid tripping in any of the transient earth fault conditions. However, if the
measured current in a phase exceeds the set value
I01
and the respective
underimpedance loop has also picked up, the distance measuring loop of that loop
is released immediately. This is done in order to clear the high current faults
instantaneously. Phase-to-phase fault loop is released if there is output from the
under impedance starting and there is no residual overcurrent start output.
I0MinPhSel
: This is the minimum current that should be present to detect a phase-
to-phase fault. The recommended setting is 4.0%
IB
.
ModeI0StRel
: This is used to release the
L1E & L2E
/
L1L2
distance measuring
loops using the residual overcurrent start. The default setting is
L1E & L2E
.
If magnitudes of both phase currents (IL1 and IL2) are almost equal or less than the
set value
I0MinPhSel
, it indicates that a phase-to-phase fault has occurred in the
system. At this condition, the measuring loops are enabled based on the setting
mode
ModeI0StRel
and the respective loops will be released for distance
measuring.
Phase preference
GUID-9C79F56B-B4CB-4214-90D2-019DE1351F54 v2
The time steps from
t0L2
to
t6L2
listed below can be selected by
settings
OpModet0L2
to
OpModet6L2
for stub line and each
distance zone 1 to zone 6 respectively.
For faults on phase L2, after distance and direction decision is fulfilled, an alarm
will appear and the additional timers
t1L2
to
t6L2
will start. If the starting element
is reset before the expiry of (and therefore before trip) the zone timers
tPEZx
plus
1MRK 506 375-UEN A
Section 7
Impedance protection
Railway application RER670 2.2 IEC
111
Application manual
Summary of Contents for RELION RER670
Page 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 48: ...42 ...
Page 70: ...64 ...
Page 80: ...74 ...
Page 100: ...94 ...
Page 210: ...204 ...
Page 364: ...358 ...
Page 384: ...378 ...
Page 468: ...462 ...
Page 494: ...488 ...
Page 504: ...498 ...
Page 505: ...499 ...