The parameters for two-step directional phase overcurrent protection D2PTOC are
set via the local HMI or Protection and Control Manager PCM600.
Common base IED values for primary current (
IBase
), primary voltage (
UBase
)
and primary power (
SBase
) are set in the global base values for settings function
GBASVAL.
GlobalBaseSel
: This is used to select GBASVAL function for reference of base
values.
The parameter settings for the base quantities, which represent the base (100%) for
pickup levels of all measuring stages, shall be entered as setting parameters for
every D2PTOC function.
For two-phase railway supply system,
IBase
shall be entered as:
•
Rated phase current of the protected object in primary amperes, when the
measured current quantity is selected other than
phase1-phase2
, which is
shown in Table
.
•
Rated phase current of the protected object in primary amperes multiplied by
2.0 (i.e. 2.0*Iphase), when the measured current quantity is selected as
phase1- phase2
, which is shown in Table
.
For two-phase railway supply system,
UBase
shall be entered as:
•
Rated phase-to-earth voltage of the protected object in primary kV, when the
measured voltage quantity is selected other than
phase1-phase2
, which is
shown in Table
.
•
Rated phase-to-phase voltage of the protected object in primary kV, when the
measured voltage quantity is selected as
phase1-phase2
, which is shown in
Table
Operation
: This is used for two-step directional phase overcurrent protection
Off
/
On
.
CurrentInput
: This is used to select the type of energizing quantity (i.e. phasor) for
current and will be used as operating quantity for operation of both overcurrent
steps.
Table 17:
Current selection for D2PTOC function
Set value for the parameter
CurrentInput
Comment
phase1
D2PTOC function will measure the phase L1
current
phase2
D2PTOC function will measure the phase L2
current
posSeq
D2PTOC function will measure internally
calculated positive sequence current
1
2 / 2
IL
IL
Table continues on next page
Section 8
1MRK 506 375-UEN A
Current protection
162
Railway application RER670 2.2 IEC
Application manual
Summary of Contents for RELION RER670
Page 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 48: ...42 ...
Page 70: ...64 ...
Page 80: ...74 ...
Page 100: ...94 ...
Page 210: ...204 ...
Page 364: ...358 ...
Page 384: ...378 ...
Page 468: ...462 ...
Page 494: ...488 ...
Page 504: ...498 ...
Page 505: ...499 ...