RFPEFwZ1
: This is used to set the forward fault resistive reach in Ohm/p for the
phase-to-earth faults in zone 1. It should be set to give maximum coverage
considering the line resistance, arc resistance and tower footing resistance. In
general, resistive reach should be set to give maximum coverage subject to check
possibility against load point encroachment considering minimum expected voltage
and maximum load. In case of short lines, consideration has to be given to
overreach due to remote end infeed and reach in resistance direction is restricted.
RFPERvZ1
: This is used to set the reverse fault resistive reach in Ohm/p for phase-
to-earth faults in zone 1. It may be set identical to
RFPEFwZ1
.
RFPPFwZ1
: This is used to set the forward fault resistive reach in Ohm/p for
phase-to-phase faults in zone 1. It should be set to cover the arc resistance for
phase-to-phase faults.
RFPPRvZ1
: This is used to set the reverse fault resistive reach in Ohm/p for phase-
to-phase faults in zone 1. It may be set identical to
RFPPFwZ1
.
TimerSelZ1
: This is used to set the zone timer selection mode of zone 1. i.e.
Timers
separated
,
Timers linked
,
General start
,
PhSel start
,
Internal start
and
External
start
. The default setting is
Timers separated
.
OpModetPEZ1
: This is used to set the
Off/On
operation of the phase-to-earth timer
of zone 1. The default setting is
Off
.
tPEZ1
: This is used to set the time delay to trip for phase-to-earth faults in zone 1.
The default setting is 0.0s.
OpModetPPZ1
: This is used to set the
Off/On
operation of the phase-to-phase timer
of zone 1. The default setting is
Off
.
tPPZ1
: This is used to set the time delay to trip for phase-to-phase faults in zone 1.
The default setting is 0.0s.
Zone 2
GUID-DD64B7C1-6337-4AC5-995C-8C068E1E379D v2
OpZ2
: This is used for the
Off/On
operation of zone 2 and it is set to
Off
by default.
DirModeZ2
: This is used to set the zone 2 direction mode. It can be set to
Non-
directional
,
Forward
and
Reverse
. The
Forward
direction mode is set by default.
PhSelModeZ2
: This is used to enable the measuring loops of zone 2. It can be set to
Phsel logic
,
Release L1E
,
ReleaseL2E
,
Release PE
,
Release L1L2
and
Release
PE&PP
modes. The default setting is
Phsel logic
mode.
LEModeZ2
: This is used to operate the load discrimination characteristic of zone 2.
The default setting is
Off
.
LCModeZ2
: This is used to enable/disable the adaptive load compensation mode of
zone 2. It avoids overreaching of the zone in to the next section in case of resistive
fault due to remote end feed. Generally, this setting is not needed for zone 2. The
default setting is
Off
.
Section 7
1MRK 506 375-UEN A
Impedance protection
104
Railway application RER670 2.2 IEC
Application manual
Summary of Contents for RELION RER670
Page 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 48: ...42 ...
Page 70: ...64 ...
Page 80: ...74 ...
Page 100: ...94 ...
Page 210: ...204 ...
Page 364: ...358 ...
Page 384: ...378 ...
Page 468: ...462 ...
Page 494: ...488 ...
Page 504: ...498 ...
Page 505: ...499 ...