DirModeZ3
: This is used to set the zone 3 direction mode. It can be set to
Non-
directional
,
Forward
and
Reverse
. The
Forward
direction mode is set by default.
PhSelModeZ3
: This is used to enable the measuring loops of zone 3. It can be set to
Phsel logic
,
Release L1E
,
ReleaseL2E
,
Release PE
,
Release L1L2
and
Release
PE&PP
modes. The default setting is
Phsel logic
mode.
LEModeZ3
: This is used to operate the load discrimination characteristic of zone 3.
The default setting is
Off
.
LCModeZ3
: This is used to enable/disable the adaptive load compensation mode of
zone 3. It avoids overreaching of the zone in to the next section in case of resistive
fault due to remote end feed. Generally, this setting is not needed for zone 3. The
default setting is
Off
.
X1FwZ3
: This is used to set the forward positive sequence reactance reach of zone
3 in Ohm/p. It should be set to overreach the remote terminal of the longest
adjacent line by 20% for all fault conditions.
X1RvZ3
: This is used to set the reverse positive sequence impedance reach of zone
3 in Ohm/p. It may be set identical to
X1FwZ3
.
REoverRLZ3
: This is used to set the earth return compensation factor for resistance
of zone 3. It provides zero sequence compensation for phase-to-earth faults.
XEoverXLZ3
: This is used to set the earth return compensation factor for reactance
of zone 3. It provides zero sequence compensation for phase-to-earth faults.
RFPEFwZ3
: This is used to set the forward fault resistive reach in Ohm/p for the
phase-to-earth faults in zone 3. This may be set identical to zone 2 setting resistive
reach.
RFPERvZ3
: This is used to set the reverse fault resistive reach in Ohm/p for phase-
to-earth faults in zone 3. This may be set identical to zone 2 setting resistive reach.
RFPPFwZ3
: This is used to set the forward fault resistive reach in Ohm/p for
phase-to-phase faults in zone 3. This may be set identical to zone 2 setting resistive
reach.
RFPPRvZ3
: This is used to set the reverse fault resistive reach in Ohm/p for phase-
to-phase faults in zone 3. This may be set identical to zone 2 setting resistive reach.
TimerSelZ3
: This is used to set the zone timer selection mode of zone 3. i.e.
Timers
separated
,
Timers linked
,
General start
,
PhSel start
,
Internal start
and
External
start
. The default setting is
Timers separated
.
OpModetPEZ3
: This is used to set the
Off/On
operation of the phase-to-earth timer
of zone 3. The default setting is
Off
.
tPEZ3
: This is used to set the time delay to trip for phase-to-earth faults in zone 3.
It should be set so that it provides discrimination with the operating time of relays
Section 7
1MRK 506 375-UEN A
Impedance protection
106
Railway application RER670 2.2 IEC
Application manual
Summary of Contents for RELION RER670
Page 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 48: ...42 ...
Page 70: ...64 ...
Page 80: ...74 ...
Page 100: ...94 ...
Page 210: ...204 ...
Page 364: ...358 ...
Page 384: ...378 ...
Page 468: ...462 ...
Page 494: ...488 ...
Page 504: ...498 ...
Page 505: ...499 ...