8.7.2
Setting guidelines
M11546-4 v9
The parameters for Breaker failure protection CCRWRBRF application function
are set via the local HMI or Protection and Control Manager PCM600.
Common base IED values for primary current (
IBase
), primary voltage (
UBase
)
and primary power (
SBase
) are set in the global base values for settings function
GBASVAL.
GlobalBaseSel
: This is used to select GBASVAL function for reference of base
values.
Operation
: This is used for breaker failure protection
Off
/
On
.
FunctionMode
: This parameter defines the way the detection of failure of the
breaker is performed. In the mode
Current
the current measurement is used for the
detection. In the mode
Contact
the status of breaker auxiliary contact is used as
indicator of failure of the breaker. The mode
Current/Contact
means that either
criterion of detections can be activated.
Contact
mode will then be used in situation
where the fault current through the circuit breaker is small at the moment when
function is initiated (current level determined by parameter
I>BlkCont
). This can
be the case for some generator protection application (for example reverse power
protection) or in case of line ends with weak end infeed.
RetripMode
: This setting states how the re-trip function shall operate.
Retrip Off
means that the re-trip function is not activated.
CB Pos Check
(circuit breaker
position check) and
Current
means that a phase current must be larger than the
operate level to allow re-trip.
CB Pos Check
(circuit breaker position check) and
Contact
means re-trip is done when circuit breaker is closed (breaker position is
used).
No CBPos Check
means re-trip is done without any check of breaker
position.
Table 22:
Dependencies between parameters RetripMode and FunctionMode
RetripMode
FunctionMode
Description
Retrip Off
N/A
the re-trip function is not
activated
CB Pos Check
Current
re-trip is done if the phase
current is larger than the
operate level after re-trip time
has elapsed
Contact
re-trip is done when auxiliary
contact position indicates that
breaker is still closed after re-
trip time has elapsed
Current/Contact
both methods according to
above are used but taken into
account also
I>BlkCont
Table continues on next page
Section 8
1MRK 506 375-UEN A
Current protection
188
Railway application RER670 2.2 IEC
Application manual
Summary of Contents for RELION RER670
Page 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 48: ...42 ...
Page 70: ...64 ...
Page 80: ...74 ...
Page 100: ...94 ...
Page 210: ...204 ...
Page 364: ...358 ...
Page 384: ...378 ...
Page 468: ...462 ...
Page 494: ...488 ...
Page 504: ...498 ...
Page 505: ...499 ...