OCBk
: Selection of action to be taken in case any of the three phase currents on the
HV-side has exceeded
Iblock
.
MFPosDiffBk
: Selection of action to be taken in case the tap difference between a
follower and the master is greater than
MFPosDiffLim
.
OVPartBk
: Selection of action to be taken in case the busbar voltage U
B
exceeds
Umax
.
RevActPartBk
: Selection of action to be taken in case Reverse Action has been
activated.
TapChgBk
: Selection of action to be taken in case a Tap Changer Error has been
identified.
TapPosBk
: Selection of action to be taken in case of Tap Position Error, or if the tap
changer has reached an end position.
UVBk
: Selection of action to be taken in case the busbar voltage U
B
falls below
Ublock
.
UVPartBk
: Selection of action to be taken in case the busbar voltage U
B
is between
Ublock
and
Umin
.
12.5.2.2
TR1ATCC or TR8ATCC Setting group
SEMOD171501-22 v8
General
Operation
: Switching automatic voltage control for tap changer, TR1ATCC for
single control and TR8ATCC for parallel control function
On
/
Off
.
I1Base
: Base current in primary Ampere for the HV-side of the transformer.
I2Base
: Base current in primary Ampere for the LV-side of the transformer.
UBase
: Base voltage in primary kV for the LV-side of the transformer.
MeasMode
: Selection of single phase, or phase-phase, or positive sequence
quantity to be used for voltage and current measurement on the LV-side. The
involved phases are also selected. Thus, single phase as well as phase-phase or
three-phase feeding on the LV-side is possible but it is commonly selected for
current and voltage.
Q1
,
Q2
and
Q3
: Mvar value of a capacitor bank or reactor that is connected
between the power transformer and the CT, such that the current of the capacitor
bank (reactor) needs to be compensated for in the calculation of circulating
currents. There are three independent settings
Q1
,
Q2
and
Q3
in order to make
possible switching of three steps in a capacitor bank in one bay.
Section 12
1MRK 506 375-UEN A
Control
322
Railway application RER670 2.2 IEC
Application manual
Summary of Contents for RELION RER670
Page 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 48: ...42 ...
Page 70: ...64 ...
Page 80: ...74 ...
Page 100: ...94 ...
Page 210: ...204 ...
Page 364: ...358 ...
Page 384: ...378 ...
Page 468: ...462 ...
Page 494: ...488 ...
Page 504: ...498 ...
Page 505: ...499 ...