X1FwZ6
: This is used to set the forward positive sequence reactance reach of zone
6 in Ohm/p. It may be set identical to zone 2 reach setting.
X1RvZ6
: This is used to set the reverse positive sequence impedance reach of zone
6 in Ohm/p. It may be set less than zone 1 reach of distance protection for the
shortest line in the reverse direction.
REoverRLZ6
: This is used to set the earth return compensation factor for resistance
of zone 6. It provides zero sequence compensation for phase-to-earth faults.
XEoverXLZ6
: This is used to set the earth return compensation factor for reactance
of zone 6. It provides zero sequence compensation for phase-to-earth faults.
RFPEFwZ6
: This is used to set the forward fault resistive reach in Ohm/p for the
phase-to-earth faults of zone 6. It may be set identical to zone 2 resistive reach
setting.
RFPERvZ6
: This is used to cover the zone 6 fault resistive reach in Ohm/p for
phase-to-earth faults in reverse direction. It should be set identical to zone 2
resistive reach setting.
RFPPFwZ6
: This is used to set the forward fault resistive reach in Ohm/p for
phase-to-phase faults of zone 6. It should be set identical to zone 2 resistive reach
setting.
RFPPRvZ6
: This is used to cover the zone 6 fault resistive reach in Ohm/p for
phase-to-phase faults in reverse direction. It should be set identical to zone 2
resistive reach setting.
TimerSelZ6
: This is used to set the zone timer selection mode of zone 6. i.e.
Timers
separated
,
Timers linked
,
General start
,
PhSel start
,
Internal start
and
External
start
. The default setting is
Timers separated
.
OpModetPEZ6
: This is used to set the
Off/On
operation of the phase-to-earth timer
of zone 6. The default setting is
Off
.
tPEZ6
: This is used to set the time delay to trip for phase-to-earth faults in zone 6.
It should be set to 0.0 s.
OpModetPPZ6
: This is used to set the
Off/On
operation of the phase-to-phase timer
of zone 6. The default setting is
Off
.
tPPZ6
: This is used to set the time delay to trip for phase-to-earth faults in zone 6.
It should be set to 0.0 s.
Phase Selection
GUID-A4027C80-5966-427E-8FFD-838A052146AE v2
ModePhSelKI
: This setting is used to enable/disable current ratio of the phase
currents. The default setting is
Off
.
KI
: The current ratio of phase currents used for phase selection. The recommended
setting is 2.0.
Section 7
1MRK 506 375-UEN A
Impedance protection
110
Railway application RER670 2.2 IEC
Application manual
Summary of Contents for RELION RER670
Page 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 48: ...42 ...
Page 70: ...64 ...
Page 80: ...74 ...
Page 100: ...94 ...
Page 210: ...204 ...
Page 364: ...358 ...
Page 384: ...378 ...
Page 468: ...462 ...
Page 494: ...488 ...
Page 504: ...498 ...
Page 505: ...499 ...