The characteristic angle of the directional functions
RCADir
is set in degrees.
RCADir
is normally set equal to 0° in a high impedance earthed network with a
neutral point resistor as the active current component is appearing out on the
faulted feeder only.
RCADir
is set equal to -90° in an isolated network as all
currents are mainly capacitive.
ROADir
is Relay Operating Angle.
ROADir
is identifying a window around the
reference direction in order to detect directionality.
ROADir
is set in degrees. For
angles differing more than
ROADir
from
RCADir
the function is blocked. The
setting can be used to prevent unwanted operation for non-faulted feeders, with
large capacitive earth fault current contributions, due to CT phase angle error.
INCosPhi>
is the operate current level for the directional function when
OpMode
is set
2I0Cosfi
. The setting is given in % of
IBase
. The setting should be based on
calculation of the active or capacitive earth fault current at required sensitivity of
the protection.
SN>
is the operate power level for the directional function when
OpMode
is set
2I02U0Cosfi
. The setting is given in % of
SBase
. The setting should be based on
calculation of the active or capacitive earth fault residual power at required
sensitivity of the protection.
The input transformer for the Sensitive directional residual over current and power
protection function has the same short circuit capacity as the phase current
transformers. Hence, there is no specific requirement for the external CT core, i.e.
any CT core can be used.
If the time delay for residual power is chosen the delay time is dependent on two
setting parameters.
SRef
is the reference residual power, given in % of
SBase
.
kSN
is the time multiplier. The time delay will follow the following expression:
0
0
2
2
cos
inv
kSN Sref
t
I
U
measured
IECEQUATION16103 V1 EN-US
(Equation 55)
INDir>
is the operate current level for the directional function when
OpMode
is set
2I0 and fi
. The setting is given in % of
IBase
. The setting should be based on
calculation of the earth fault current at required sensitivity of the protection.
OpINNonDir>
is set
On
to activate the non-directional residual current protection.
INNonDir>
is the operate current level for the non-directional function. The setting
is given in % of
IBase
. This function can be used for detection and clearance of
cross-country faults in a shorter time than for the directional function. The current
setting should be larger than the maximum single-phase residual current on the
protected line.
TimeChar
is the selection of time delay characteristic for the non-directional
residual current protection. Definite time delay and different types of inverse time
characteristics are available:
Section 8
1MRK 506 375-UEN A
Current protection
182
Railway application RER670 2.2 IEC
Application manual
Summary of Contents for RELION RER670
Page 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 48: ...42 ...
Page 70: ...64 ...
Page 80: ...74 ...
Page 100: ...94 ...
Page 210: ...204 ...
Page 364: ...358 ...
Page 384: ...378 ...
Page 468: ...462 ...
Page 494: ...488 ...
Page 504: ...498 ...
Page 505: ...499 ...