The setting for the duration of the breaker close pulse.
tMaxSynch
The setting
tMaxSynch
is set to reset the operation of the synchronizing function if
the operation does not take place within this time. The setting must allow for the
setting of
FreqDiffMin
, which will decide how long it will take maximum to reach
phase equality. At the setting of 10 mHz, the beat time is 100 seconds and the
setting would thus need to be at least
tMinSynch
plus 100 seconds. If the network
frequencies are expected to be outside the limits from the start, a margin needs to
be added. A typical setting is 600 seconds.
tMinSynch
The setting
tMinSynch
is set to limit the minimum time at which the synchronizing
closing attempt is given. The synchronizing function will not give a closing
command within this time, from when the synchronizing is started, even if a
synchronizing condition is fulfilled. A typical setting is 200 ms.
Synchrocheck settings
OperationSC
The
OperationSC
setting
Off
disables the synchrocheck function and sets the
outputs AUTOSYOK, MANSYOK, TSTAUTSY and TSTMANSY to low. With
the setting
On
, the function is in the service mode and the output signal depends on
the input conditions.
UHighBusSC
and
UHighLineSC
The voltage level settings must be chosen in relation to the bus or line network
voltage. The threshold voltages
UHighBusSC
and
UHighLineSC
have to be set
lower than the value at which the breaker is expected to close with the synchronism
check. A typical value can be 80% of the base voltages.
UDiffSC
The setting for voltage difference between line and bus in p.u. This setting in p.u. is
defined as (U-Bus/
GblBaseSelBus
) - (U-Line/
GblBaseSelLine
). A normal setting is
0,10-0,15 p.u.
FreqDiffM
and
FreqDiffA
The frequency difference level settings,
FreqDiffM
and
FreqDiffA
, shall be chosen
depending on the condition in the network. At steady conditions a low frequency
difference setting is needed, where the
FreqDiffM
setting is used. For autoreclosing
a bigger frequency difference setting is preferable, where the
FreqDiffA
setting is
used. A typical value for
FreqDiffM
can be10 mHz, and a typical value for
FreqDiffA
can be 100-200 mHz.
PhaseDiffM
and
PhaseDiffA
1MRK 506 375-UEN A
Section 12
Control
Railway application RER670 2.2 IEC
221
Application manual
Summary of Contents for RELION RER670
Page 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 48: ...42 ...
Page 70: ...64 ...
Page 80: ...74 ...
Page 100: ...94 ...
Page 210: ...204 ...
Page 364: ...358 ...
Page 384: ...378 ...
Page 468: ...462 ...
Page 494: ...488 ...
Page 504: ...498 ...
Page 505: ...499 ...