Homing (operation with the circulating current method)
SEMOD159053-205 v3
This function can be used with parallel operation of power transformers using the
circulating current method. It makes possible to keep a transformer energized from
the HV side, but open on the LV side (hot stand-by), to follow the voltage
regulation of loaded parallel transformers, and thus be on a proper tap position
when the LV circuit breaker closes.
For this function, it is needed to have the LV VTs for each transformer on the cable
(tail) side (not the busbar side) of the CB, and to have the LV CB position
hardwired to the IED.
In TR8ATCC block for one transformer, the state "Homing" will be defined as the
situation when the transformer has information that it belongs to a parallel group
(for example, information on T1INCLD=1 or T2INCLD=1 ... and so on), at the
same time as the binary input DISC on TR8ATCC block is activated by open LV
CB. If now the setting parameter
OperHoming
=
On
for that transformer,
TR8ATCC will act in the following way:
•
The algorithm calculates the “true” busbar voltage, by averaging the voltage
measurements of the other transformers included in the parallel group (voltage
measurement of the “disconnected transformer” itself is not considered in the
calculation).
•
The value of this true busbar voltage is used in the same way as U
set
for
control of a single transformer. The “disconnected transformer” will then
automatically initiate URAISE or ULOWER commands (with appropriate
t1
or
t2
time delay) in order to keep the LV side of the transformer within the
deadband of the busbar voltage.
Homing (operation with the master follower method)
SEMOD159053-216 v3
If one (or more) follower has its LV circuit breaker open and its HV circuit breaker
closed, and if
OperHoming
=
On
, this follower continues to follow the master just
as it would have made with the LV circuit breaker closed. On the other hand, if the
LV circuit breaker of the master opens, automatic control will be blocked and
TR8ATCC function output MFERR will be activated as the system will not have a
master.
Adapt mode, manual control of a parallel group
SEMOD159053-219 v2
Adapt mode (operation with the circulating current method)
SEMOD159053-221 v5
When the circulating current method is used, it is also possible to manually control
the transformers as a group. To achieve this, the setting
OperationAdapt
must be
set
On
, then the control mode for one TR8ATCC shall be set to “Manual” via the
binary input MANCTRL or the local HMI under
Main menu/Control/
Commands/TransformerVoltageControl(ATCC,90)/TR8ATCC:x
whereas the
other TR8ATCCs are left in “Automatic”. TR8ATCCs in automatic mode will then
observe that one transformer in the parallel group is in manual mode and will then
automatically be set in adapt mode. As the name indicates they will adapt to the
manual tapping of the transformer that has been put in manual mode.
Section 12
1MRK 506 375-UEN A
Control
304
Railway application RER670 2.2 IEC
Application manual
Summary of Contents for RELION RER670
Page 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 48: ...42 ...
Page 70: ...64 ...
Page 80: ...74 ...
Page 100: ...94 ...
Page 210: ...204 ...
Page 364: ...358 ...
Page 384: ...378 ...
Page 468: ...462 ...
Page 494: ...488 ...
Page 504: ...498 ...
Page 505: ...499 ...