Table 38:
General settings parameters for the Measurement function
Setting
Short Description
Selected
value
Comments
Operation
Operation Off/On
On
Function must be
On
k
Low pass filter coefficient for
power measurement, U and I
0.00
Typically no additional filtering is
required
UGenZeroDb
Zero point clamping in % of
Ubase
25
Set minimum voltage level to
25%. Voltage below 25% will
force S, P and Q to zero.
IGenZeroDb
Zero point clamping in % of
Ibase
3
Set minimum current level to 3%.
Current below 3% will force S, P
and Q to zero.
UBase (set in
Global base)
Base setting for voltage level in
kV
110.00
Set rated OHL phase-to-phase
voltage
IBase (set in
Global base)
Base setting for current level in
A
600
Set rated primary CT current
used for OHL
SBase (set in
Global base)
Base setting for power level in
MVA
66
Set rated apparent two-phase
power which correspond to
110kV and 600A
Table 39:
Settings parameters for level supervision
Setting
Short Description
Selected
value
Comments
PMin
Minimum value
-100
Minimum expected load
PMax
Maximum value
100
Maximum expected load
PZeroDb
Zero point clamping in 0.001% of
range
1000
Set zero point clamping to 0,66
MW that is, 1% of 66 MW
PRepTyp
Reporting type
db
Select amplitude deadband
supervision
PDbRepInt
Cycl: Report interval (s), Db: In
% of range, Int Db: In %s
5
Set ±Δdb=1,3 MW that is, 2%
(larger changes than 1,3 MW will
be reported)
PHiHiLim
High High limit (physical value)
120
High alarm limit that is, extreme
overload alarm
PHiLim
High limit (physical value)
100
High warning limit that is,
overload warning
PLowLim
Low limit (physical value)
-100
Low warning limit. Not active
PLowLowlLim
Low Low limit (physical value)
-120
Low alarm limit. Not active
PLimHyst
Hysteresis value in % of range
(common for all limits)
2
Set ±Δ Hysteresis MW that is,
2%
Measurement function application for a power transformer
SEMOD54481-61 v9
Single line diagram for this application is given in Figure
.
Section 15
1MRK 506 375-UEN A
Monitoring
386
Railway application RER670 2.2 IEC
Application manual
Summary of Contents for RELION RER670
Page 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 48: ...42 ...
Page 70: ...64 ...
Page 80: ...74 ...
Page 100: ...94 ...
Page 210: ...204 ...
Page 364: ...358 ...
Page 384: ...378 ...
Page 468: ...462 ...
Page 494: ...488 ...
Page 504: ...498 ...
Page 505: ...499 ...