![ABB RELION RER670 Applications Manual Download Page 302](http://html.mh-extra.com/html/abb/relion-rer670/relion-rer670_applications-manual_4708302.webp)
1. Automatic load voltage adjustment, proportional to the load current.
2. Constant load voltage adjustment with four different preset values.
In the first case the voltage adjustment is dependent on the load and maximum
voltage adjustment should be obtained at rated load of the transformer.
In the second case, a voltage adjustment of the set point voltage can be made in
four discrete steps (positive or negative) activated with binary signals connected to
TR1ATCC or TR8ATCC function block inputs LVA1, LVA2, LVA3 and LVA4. The
corresponding voltage adjustment factors are given as setting parameters
LVAConst1
,
LVAConst2
,
LVAConst3
and
LVAConst4
. The inputs are activated with
a pulse, and the latest activation of anyone of the four inputs is valid. Activation of
the input LVARESET in TR1ATCC or TR8ATCC block, brings the voltage setpoint
back to
USet
.
With these factors, TR1ATCC or TR8ATCC adjusts the value of the set voltage
USet
according to the following formula:
2
L
a
ci
I
Usetadjust Uset S
S
I Base
=
+ ×
+
IECEQUATION1978 V1 EN-US
(Equation 70)
U
set, adjust
Adjusted set voltage in per unit
USet
Original set voltage: Base quality is U
n2
S
a
Automatic load voltage adjustment factor, setting
VRAuto
I
L
Load current
I2Base
Rated current, LV winding
S
ci
Constant load voltage adjust. factor for active input
i (corresponding to
LVAConst1, LVAConst2, LVAConst3 and LVAConst4)
It shall be noted that the adjustment factor is negative in order to decrease the load
voltage and positive in order to increase the load voltage. After this calculation
U
set, adjust
will be used by TR1ATCC or TR8ATCC for voltage regulation instead of
the original value
USet
. The calculated set point voltage U
Set, adjust
is shown on the
local HMI as a service value under
Main menu/Test/Function status/Control/
TransformerVoltageControl(ATCC,90)/TR1ATCC:x/TR8ATCC:x
.
Automatic control of parallel transformers
SEMOD159053-135 v5
Control of parallel transformers means control of two or more power transformers
connected to the same busbar on the LV side and in most cases also on the HV
side. Special measures must be taken in order to avoid a runaway situation where
the tap changers on the parallel transformers gradually diverge and end up in
opposite end positions.
Three alternative methods can be used for parallel control with the Automatic
voltage control for tap changer, single/parallel control TR8ATCC:
Section 12
1MRK 506 375-UEN A
Control
296
Railway application RER670 2.2 IEC
Application manual
Summary of Contents for RELION RER670
Page 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 48: ...42 ...
Page 70: ...64 ...
Page 80: ...74 ...
Page 100: ...94 ...
Page 210: ...204 ...
Page 364: ...358 ...
Page 384: ...378 ...
Page 468: ...462 ...
Page 494: ...488 ...
Page 504: ...498 ...
Page 505: ...499 ...