IEC16000072 V1 EN-US
Figure 79:
Configuration with XLNPROXY and GOOSEXLNRCV where only
the mandatory data in the IEC 61850 modelling is used
All the information from the XLNPROXY to the SCSWI about command
following status, causes for failed command and selection status is transferred in
the output XPOS. The other outputs may be used by other functions in the same
way as the corresponding outputs of the SXCBR and SXSWI function.
When a command has been issued from the connected SCSWI function, the
XLNPROXY function awaits the response on it from the represented switch
through the inputs POSVAL and OPOK. While waiting for the switch to start
moving, it checks if the switch is blocked for the operation. When the switch has
started moving and no blocking condition has been detected, XLNPROXY issues a
response to the SCSWI function that the command has started. If OPOK is used,
this response is given when XLNPROXY receives the signal.
If no movement of the switch is registered within the limit
tStartMove
, the
command is considered failed, and the cause of the failure is evaluated. In the
evaluation, the function checks if the state of the represented switch is indicating
that the command is blocked in any way during the command, and gives the
appropriate cause to the SCSWI function. This cause is also shown on the output
L_CAUSE as indicated in the following table:
1MRK 506 375-UEN A
Section 12
Control
Railway application RER670 2.2 IEC
245
Application manual
Summary of Contents for RELION RER670
Page 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 48: ...42 ...
Page 70: ...64 ...
Page 80: ...74 ...
Page 100: ...94 ...
Page 210: ...204 ...
Page 364: ...358 ...
Page 384: ...378 ...
Page 468: ...462 ...
Page 494: ...488 ...
Page 504: ...498 ...
Page 505: ...499 ...