![ABB RELION RER670 Applications Manual Download Page 448](http://html.mh-extra.com/html/abb/relion-rer670/relion-rer670_applications-manual_4708448.webp)
IED
IED
IED
Substation LAN
IEC05000715-4-en.vsd
Remote
monitoring
Utility LAN
WAN
IEC05000715 V4 EN-US
Figure 187:
SPA communication structure for a remote monitoring system via a
substation LAN, WAN and utility LAN
SPA communication is mainly used for the Station Monitoring System. It can
include different IEDs with remote communication possibilities. Connection to a
PC can be made directly (if the PC is located in the substation), via a telephone
modem through a telephone network with ITU (former CCITT) characteristics or
via a LAN/WAN connection.
glass
<1000 m according to optical budget
plastic
<25 m (inside cubicle) according to optical budget
Functionality
SEMOD115767-25 v2
The SPA protocol V2.5 is an ASCII-based protocol for serial communication. The
communication is based on a master-slave principle, where the IED is a slave and
the PC is the master. Only one master can be applied on each fibre optic loop. A
program is required in the master computer for interpretation of the SPA-bus codes
and for translation of the data that should be sent to the IED.
For the specification of the SPA protocol V2.5, refer to SPA-bus Communication
Protocol V2.5.
18.5.2
Setting guidelines
M11876-3 v6
SPA, IEC 60870-5-103 and DNP3 use the same rear communication port. This port
can be set for SPA use on the local HMI under
Main menu /Configuration /
Communication /Station communication/Port configuration/SLM optical
serial port/PROTOCOL:1
. When the communication protocol is selected, the
IED is automatically restarted, and the port then operates as a SPA port.
The SPA communication setting parameters are set on the local HMI under
Main
menu/Configuration/Communication/Station communication/SPA/SPA:1
.
Section 18
1MRK 506 375-UEN A
Station communication
442
Railway application RER670 2.2 IEC
Application manual
Summary of Contents for RELION RER670
Page 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 48: ...42 ...
Page 70: ...64 ...
Page 80: ...74 ...
Page 100: ...94 ...
Page 210: ...204 ...
Page 364: ...358 ...
Page 384: ...378 ...
Page 468: ...462 ...
Page 494: ...488 ...
Page 504: ...498 ...
Page 505: ...499 ...