The current detected shall be active if all phase currents are higher than the
setting.
7.
Set
CurrUnsymLevel
to
80%
.
Pole discordance is detected if the magnitude of the lowest phase current is lower
than the fraction
CurrUnsymLevel
(%) of the highest phase current.
Section 3
1MRK 505 291-UEN A
REQ650 setting examples
60
Application manual