With the setting
On
, the function is in service and the output signal depends on the
input conditions.
UDiffSC
Setting for voltage difference between line and bus in p.u. This setting in p.u is defined
as (measured U-Bus/UBase for bus according to
GblBaseSelBus
) - (measured U-Line/
UBase for line according to
GblBaseSelLine
). A typical value for the voltage
difference can be 15%.
FreqDiffM
and
FreqDiffA
The frequency difference level settings,
FreqDiffM
and
FreqDiffA
, shall be chosen
depending on the condition in the network. At steady conditions a low frequency
difference setting is needed, where the
FreqDiffM
setting is used. For auto-reclosing
a bigger frequency difference setting is preferable, where the
FreqDiffA
setting is
used. A typical value for the
FreqDiffM
can
10
mHz and a typical value for the
FreqDiffA
can be
100-200
mHz, when the synchronizing function is not used.
PhaseDiffM
and
PhaseDiffA
The phase angle difference level settings,
PhaseDiffM
and
PhaseDiffA
, shall also be
chosen depending on conditions in the network. The phase angle setting must be
chosen to allow closing under maximum load. A typical maximum value in heavy-
loaded networks can be 45 degrees whereas in most networks the maximum occurring
angle is below 25 degrees. The setting of
PhaseDiffA
setting is limited by the
PhaseDiffM
setting.
tSCM
and
tSCA
The purpose of the timer delay settings,
tSCM
and
tSCA
, is to ensure that the
synchrocheck conditions remains constant and that the situation is not due to a
temporary interference. Should the conditions not persist for the specified time, the
delay timer is reset and the procedure is restarted when the conditions are fulfilled
again. Circuit breaker closing is thus not permitted until the synchrocheck situation
has remained constant throughout the set delay setting time. Under stable conditions
a longer operation time delay setting is needed, where the
tSCM
setting is used. During
auto-reclosing a shorter operation time delay setting is preferable, where the
tSCA
setting is used. A typical value for the
tSCM
may be
1
second and a typical value for the
tSCA
may be
0.1
second.
Energizing check settings
AutoEnerg
and
ManEnerg
Two different settings can be used for automatic and manual closing of the circuit
breaker. The settings for each of them are:
•
Off
, the energizing function is disabled.
•
DLLB
, Dead Line Live Bus: the line voltage is below 40% of the line base voltage
UBase
according to the setting
GblBaseSelLine
about the Global Base Value
Section 10
1MRK 505 291-UEN A
Control
196
Application manual
Summary of Contents for Relion REQ650
Page 1: ...Relion 650 series Breaker protection REQ650 Application manual ...
Page 2: ......
Page 20: ...14 ...
Page 26: ...20 ...
Page 48: ...42 ...
Page 82: ...76 ...
Page 90: ...84 ...
Page 160: ...154 ...
Page 178: ...172 ...
Page 264: ...258 ...
Page 288: ...282 ...
Page 302: ...296 ...
Page 330: ...324 ...
Page 338: ...332 ...
Page 339: ...333 ...