time base for the IEDs in a protection and control system. This makes comparison and
analysis of events and disturbance data between all IEDs in the power system possible.
Time-tagging of internal events and disturbances are an excellent help when
evaluating faults. Without time synchronization, only the events within the IED can
be compared to one another. With time synchronization, events and disturbances
within the entire station, and even between line ends, can be compared during
evaluation.
In the IED, the internal time can be synchronized from a number of sources:
•
SNTP
•
IRIG-B
•
DNP
•
IEC60870-5-103
Micro SCADA OPC server should not be used as a time
synchronization source.
15.2.3
Setting guidelines
System time
The time is only possible to set inside the IED via the local HMI by navigating to
Configuration/Time/SYSTEMTIME
with year, month, day, hour, minute and
second.
Synchronization
With external time synchronization the setting how to synchronize for the real-time
clock (TIME) are set via local HMI or PCM600.
TimeSynch
The setting
TIMESYNCGEN
is used to set the source of the time synchronization. The
setting alternatives are:
CoarseSyncSrc
which can have the following values:
•
Off
•
SNTP
•
DNP
•
IEC60870-5-103
FineSyncSource
which can have the following values:
1MRK 505 291-UEN A
Section 15
Basic IED functions
299
Application manual
Summary of Contents for Relion REQ650
Page 1: ...Relion 650 series Breaker protection REQ650 Application manual ...
Page 2: ......
Page 20: ...14 ...
Page 26: ...20 ...
Page 48: ...42 ...
Page 82: ...76 ...
Page 90: ...84 ...
Page 160: ...154 ...
Page 178: ...172 ...
Page 264: ...258 ...
Page 288: ...282 ...
Page 302: ...296 ...
Page 330: ...324 ...
Page 338: ...332 ...
Page 339: ...333 ...