IEC09000025-1-en.vsd
~
~
Z
A
Z
B
Z
L1
A
B
I
M
Fault
IED
Z
L2
M
C
Line 1
Line 2
IEC09000025 V1 EN
Figure 58:
Two parallel lines. Influence from parallel line to the through fault
current: I
M
The minimum theoretical current setting (Imin) will in this case be:
I m in
M A X I
fA
I
fB
I
M
,
,
(
)
³
EQUATION287 V1 EN
(Equation 27)
Where:
I
fA
and I
fB
have been described for the single line case.
Considering the safety margins mentioned previously, the minimum setting (Is) is:
m
1.3.I
s
in
I
³
EQUATION288 V2 EN
(Equation 28)
Transformer inrush current shall be considered.
The setting of the protection is set as a percentage of the base current (
IBase
).
Operation
: set the protection to
On
or
Off
.
IN>>
: Set operate current in % of
IBase
.
IBase
is a global parameter valid for all
functions in the IED.
6.6
Four step residual overcurrent protection, zero,
negative sequence direction EF4PTOC
1MRK 505 291-UEN A
Section 6
Current protection
115
Application manual