Application 1: Line bay in a solidly earthed network, connected to single busbar
switchyard
•
Application 2: Line bay in a high impedance earthed network, connected to single
busbar switchyard
•
Application 3: Line bay in a solidly earthed network, connected to double busbar
switchyard
•
Application 4: Line bay in a high impedance earthed network, connected to
double busbar switchyard
The following application examples, describe transformer bay alternatives:
•
Application 5: Transformer bay in a solidly earthed network, connected to single
busbar switchyard
•
Application 6: Transformer bay in a solidly earthed network, connected to double
busbar switchyard
•
Application 7: Transformer bay in a high impedance earthed network, connected
to single busbar switchyard
2.3.2
Line bay in a solidly earthed network, connected to single
busbar switchyard
3
3
1
REQ650 (A01)/(A11)
Line/Feeder
IEC10000134-1-en.vsd
IEC10000134 V1 EN
Figure 5:
Line bay in a solidly earthed network
REQ650 has a number of back-up protection functions. In addition to this, three-phase
trip and autoreclosing is available for REQ650 (A01) and single-phase trip and
autoreclosing is available for REQ650 (A11).
Section 2
1MRK 505 291-UEN A
Application
32
Application manual
Summary of Contents for Relion REQ650
Page 1: ...Relion 650 series Breaker protection REQ650 Application manual ...
Page 2: ......
Page 20: ...14 ...
Page 26: ...20 ...
Page 48: ...42 ...
Page 82: ...76 ...
Page 90: ...84 ...
Page 160: ...154 ...
Page 178: ...172 ...
Page 264: ...258 ...
Page 288: ...282 ...
Page 302: ...296 ...
Page 330: ...324 ...
Page 338: ...332 ...
Page 339: ...333 ...