
1
PSM
2
Rs
(+)
(-)
HW
S W
PO1
TCS1
IS
V
IS: Constant current generator.
Current level ~ 1,0 mA (I
c
)
V: Transient Voltage Suppressor
Breakdown Voltage 380 to 400 VDC
I
c
CBPOS_open
TCSSCBR
TCS_STATE
BLOCK
ALARM
IEC13000026-2-en.vsd
GUID-6B09F9C7-86D0-4A7A-8E08-8E37CAE53249 V3 EN
Figure 77:
Operating principle of the trip-circuit supervision without an external
resistor. The circuit breaker open indication is set to block TCSSCBR
when the circuit breaker is open.
Trip-circuit supervision and other trip contacts
It is typical that the trip circuit contains more than one trip contact in parallel, for
example in transformer feeders where the trip of a Buchholz relay is connected in
parallel with the feeder terminal and other relays involved.
GUID-7264738C-F9D7-48F0-B6FC-F85FD10D5B84 V1 EN
Figure 78:
Constant test current flow in parallel trip contacts and trip-circuit
supervision
Section 9
1MRK 505 291-UEN A
Secondary system supervision
180
Application manual
Summary of Contents for Relion REQ650
Page 1: ...Relion 650 series Breaker protection REQ650 Application manual ...
Page 2: ......
Page 20: ...14 ...
Page 26: ...20 ...
Page 48: ...42 ...
Page 82: ...76 ...
Page 90: ...84 ...
Page 160: ...154 ...
Page 178: ...172 ...
Page 264: ...258 ...
Page 288: ...282 ...
Page 302: ...296 ...
Page 330: ...324 ...
Page 338: ...332 ...
Page 339: ...333 ...