10.1.3.3
Single circuit breaker with double busbar, internal voltage selection
Bus 1
Bus 2
QB1
QB2
Line
QA1
Fuse
VT
Fuse
VT
IEC09000738-2-en.vsd
SMAI
GRP_OFF
SMAI
SMAI
UBus1
UBus2
ULine
Fuse
VT
SESRSYN
U3PBB1*
U3PBB2*
U3PLN1*
U3PLN2*
BLOCK
BLKSYNCH
BLKSC
BLKENERG
B1QOPEN
B1QCLD
B2QOPEN
B2QCLD
LN1QOPEN
LN1QCLD
LN2QOPEN
LN2QCLD
UB1OK
UB1FF
UB2OK
UB2FF
ULN1OK
ULN1FF
ULN2OK
ULN2FF
STARTSYN
TSTSYNCH
TSTSC
TSTENERG
AENMODE
MENMODE
SYNOK
AUTOSYOK
AUTOENOK
MANSYOK
MANENOK
TSTSYNOK
TSTAUTSY
TSTMANSY
TSTENOK
USELFAIL
B1SEL
B2SEL
LN1SEL
LN2SEL
SYNPROGR
SYNFAIL
FRDIFSYN
FRDERIVA
UOKSC
UDIFFSC
FRDIFFA
PHDIFFA
FRDIFFM
PHDIFFM
INADVCLS
UDIFFME
FRDIFFME
PHDIFFME
UBUS
ULINE
MODEAEN
MODEMEN
IEC09000738 V2 EN
Figure 85:
Connection of the SESRSYN function block in a single breaker,
double busbar arrangement with internal voltage selection.
When internal voltage selection is needed, the voltage transformer circuit connections
are made according to figure
. The voltage from busbar1 VT is connected to
U3PBB1 and the voltage from busbar2 VT is connected to U3PBB2. The voltage from
the line VT is connected to U3PLN1. The positions of the disconnectors and VT fuses
shall be connected as shown in figure
. The voltage selection parameter
CBConfig
is set to
Double bus
.
10.1.4
Setting guidelines
The setting parameters for the Synchronizing, synchrocheck and energizing check
function SESRSYN are set via the local HMI (LHMI) or PCM600.
This setting guidelines describes the settings of the SESRSYN function via the LHMI.
Common base IED value for primary voltage (
UBase
) is set in a Global base value
function, GBASVAL, found under
Main menu/Configuration/Power system/
Global base values/X:GBASVAL/UBase
. GBASVAL has six instances which can
be set independently of each other. The SESRSYN function has one setting for the bus
reference voltage (
GblBaseSelBus
) and one setting for the line reference voltage
(
GblBaseSelLine
) which independently of each other can be set to select one of the six
GBASVAL functions used for reference of base values. This means that the reference
voltage of bus and line can be set to different values. The settings for the SESRSYN
function found under
Main menu/Settings/Control/SESRCYN(25,SYNC)/
Section 10
1MRK 505 291-UEN A
Control
192
Application manual
Summary of Contents for Relion REQ650
Page 1: ...Relion 650 series Breaker protection REQ650 Application manual ...
Page 2: ......
Page 20: ...14 ...
Page 26: ...20 ...
Page 48: ...42 ...
Page 82: ...76 ...
Page 90: ...84 ...
Page 160: ...154 ...
Page 178: ...172 ...
Page 264: ...258 ...
Page 288: ...282 ...
Page 302: ...296 ...
Page 330: ...324 ...
Page 338: ...332 ...
Page 339: ...333 ...