IEC12000202-1-en.vsd
IEC12000202 V1 EN
Figure 121:
PCM600 user management tool
15.12.2.1
Authorization handling in the IED
At delivery the default user is the SuperUser. No Log on is required to operate the IED
until a user has been created with the IED User Management..
Once a user is created and written to the IED, that user can perform a Log on, using the
password assigned in the tool. Then the default user will be Guest.
If there is no user created, an attempt to log on will display a message box: “No user
defined!”
If one user leaves the IED without logging off, then after the timeout (set in
Main
menu/Configuration/HMI/Screen/SCREEN:1
) elapses, the IED returns to Guest
state, when only reading is possible. By factory default, the display timeout is set to 60
minutes.
If one or more users are created with the IED User Management and written to the
IED, then, when a user attempts a Log on by pressing the
key or when the user
attempts to perform an operation that is password protected, the Log on window
opens.
Section 15
1MRK 505 291-UEN A
Basic IED functions
312
Application manual