I>
I>
A1
B1
Feeder
Time axis
t=0
t=t
1
t=t
2
t=t
3
The fault
occurs
Protection
B1 trips
Breaker at
B1 opens
Protection
A1 resets
IEC10000279-1-en.vsd
IEC10000279 V1 EN
Figure 55:
Sequence of events during fault
where:
•
t=0 is when the fault occurs.
•
t=t1 is when the trip signal from the overcurrent protection at IED B1 is sent to the
circuit breaker. The operation time of this protection is
•
t1, t=t2 is when the circuit breaker at IED B1 opens. The circuit breaker opening
time is t2 - t1.
•
t=t3 is when the overcurrent protection at IED A1 resets. The protection resetting
time is t3 - t2.
To ensure that the overcurrent protection at IED A1, is selective to the overcurrent
protection at IED B1, the minimum time difference must be larger than the time t
3
.
There are uncertainties in the values of protection operation time, breaker opening
time and protection resetting time. Therefore a safety margin has to be included. With
normal values the needed time difference can be calculated according to equation
40
100
40
40
220
t
ms
ms
ms
ms
ms
D ³
+
+
+
=
EQUATION1266 V1 EN
(Equation 24)
where it is considered that:
•
the operate time of overcurrent protection B1 is 40 ms
•
the breaker open time is 100 ms
•
the resetting time of protection A1 is 40 ms
•
the additional margin is 40 ms
Section 6
1MRK 505 291-UEN A
Current protection
112
Application manual
Summary of Contents for Relion REQ650
Page 1: ...Relion 650 series Breaker protection REQ650 Application manual ...
Page 2: ......
Page 20: ...14 ...
Page 26: ...20 ...
Page 48: ...42 ...
Page 82: ...76 ...
Page 90: ...84 ...
Page 160: ...154 ...
Page 178: ...172 ...
Page 264: ...258 ...
Page 288: ...282 ...
Page 302: ...296 ...
Page 330: ...324 ...
Page 338: ...332 ...
Page 339: ...333 ...