The function shall not operate for any of the calculated currents to the protection. The
minimum theoretical current setting (Imin) will be:
Imin MAX I
fA
I
fA
,
(
)
³
EQUATION284 V1 EN
(Equation 25)
A safety margin of 5% for the maximum static inaccuracy and a safety margin of 5%
for maximum possible transient overreach have to be introduced. An additional 20%
is suggested due to inaccuracy of instrument transformers under transient conditions
and inaccuracy in the system data.
The minimum primary current setting (Is) is:
m
1.3.I
s
in
I
³
EQUATION285 V2 EN
(Equation 26)
In case of parallel lines with zero sequence mutual coupling a fault on the parallel line,
as shown in figure
, should be calculated.
Section 6
1MRK 505 291-UEN A
Current protection
114
Application manual