setting
RCADir
to value
+65 degrees
, that is, the negative sequence current
typically lags the inverted negative sequence voltage for this angle during the
fault
•
setting
ROADir
to value
90 degrees
•
setting
LowVolt_VM
to value
2%
, that is, the negative sequence voltage level
above which the directional element will be enabled
•
setting
Operation_OC1
to
On
•
setting
StartCurr_OC1
to value between
3-10%
, (typical values)
•
setting
tDef_OC1
to insure proper time coordination with other earth-fault
protections installed in the vicinity of this power line
•
setting
DirMode_OC1
to
Forward
•
setting
DirPrinc_OC1
to
IcosPhi&U
•
setting
ActLowVolt1_VM
to
Block
DNSPTOC is used in directional comparison protection scheme for the power line
protection, when communication channels to the remote end of this power line are
available. In that case, two negative sequence overcurrent steps are required - one in
forward and another in reverse direction. The OC1 stage is used to detect faults in
forward direction and the OC2 stage is used to detect faults in reverse direction.
However, the following must be noted for such application:
•
setting
RCADir
and
ROADir
are applicable for both steps OC1 and OC2
•
setting
DirMode_OC1
must be set to
Forward
•
setting
DirMode_OC2
must be set to
Reverse
•
setting
StartCurr_OC2
must be made more sensitive than
pickup
value of the
forward OC1 element, that is, typically 60% of
StartCurr_OC1
set pickup level
in order to insure proper operation of the directional comparison scheme during
current reversal situations
•
the start signals STOC1 and STOC2 from OC1 and OC2 elements is used to send
forward and reverse signals to the remote end of the power line
•
the available scheme communications function block within IED is used between
the protection function and the teleprotection communication equipment, in
order to insure proper conditioning of the above two start signals.
ActLowVolt1
and
ActLowVolt2
should not be set to
Memory
.
1MRK 505 291-UEN A
Section 6
Current protection
153
Application manual
Summary of Contents for Relion REQ650
Page 1: ...Relion 650 series Breaker protection REQ650 Application manual ...
Page 2: ......
Page 20: ...14 ...
Page 26: ...20 ...
Page 48: ...42 ...
Page 82: ...76 ...
Page 90: ...84 ...
Page 160: ...154 ...
Page 178: ...172 ...
Page 264: ...258 ...
Page 288: ...282 ...
Page 302: ...296 ...
Page 330: ...324 ...
Page 338: ...332 ...
Page 339: ...333 ...