2.6 85
2
2
10 2.5
17.5
ph
sc
sc
line
U
I
kA
Z
Z
j
j
=
×
=
×
=
Ð °
+
+
+
EQUATION2342 V1 EN
3
3
1
REQ650 (A01)
Z
SC
: High
Ph – ph short circuit
IEC10000147-1-en.vsd
IEC10000147 V1 EN
Figure 13:
Fault for step 1 setting
In case of a three-phase short circuit in zone 1 reach in the shortest line from the remote
busbar as shown in figure
, the current to the protection is I = 1.5 kA.
Section 3
1MRK 505 291-UEN A
REQ650 setting examples
48
Application manual