3
3
1
REQ650 (A01)
Z
SC
: Low
Three-phase short circuit
Line protection zone 1 reach
IEC10000148-1-en.vsd
IEC10000148 V1 EN
Figure 14:
Fault for step 1 setting
Recommended current setting is therefore 2000 A.
1.
Set
DirMode1
to
Forward
.
2.
Set
Characterist1
to
IEC Def. Time
.
For the time delay characteristic, definite time is used in this network.
3.
Set
I1>
to
200%
of
IBase
(2000 A primary current).
4.
Set
t1
to
0.4 s
.
3.1.5.3
Calculating settings for step 2
The protection shall be able to detect all short circuits in the own busbar. A two-phase
short circuit in the busbar and high source impedance from the remote line end, as
shown in figure
, results in the following fault current for the protection:
145
3
3
3
2.6 85
2
2
10 2.5
17.5
ph
sc
sc
line
U
I
kA
Z
Z
j
j
=
×
=
×
=
Ð °
+
+
+
EQUATION2343 V1 EN
1MRK 505 291-UEN A
Section 3
REQ650 setting examples
49
Application manual