Note/illustration
Action
D
C
A
B
xx1700000741
Connect the wires according to the illus-
tration. Use a four-indent crimp tool to
make the connection tight.
2
For single phase:
A X0.1 Line (L1)
B X0.2 Neutral (N) or Live (L2)
C Not used
D X0.PE Protective Earth (PE), ground-
ing
xx1900000045
Fit the cable through the gland and the
crown clamp of the connector.
3
xx1900000046
Strip the outer cover of the cable about
27 mm.
4
xx1900000047
Strip the shielding copper wires of the
cable about 27 mm if needed.
5
xx1900000048
Strip the insulation of the wires about 7
mm.
6
Continues on next page
94
Product manual - OmniCore C30
3HAC060860-001 Revision: P
© Copyright 2019-2022 ABB. All rights reserved.
3 Installation and commissioning
3.5.4 Fitting the connector
Continued