![ABB OmniCore C30 Product Manual Download Page 520](http://html.mh-extra.com/html/abb/omnicore-c30/omnicore-c30_product-manual_3131520.webp)
Location of LEDs
xx1700001886
Detailed working procedure
Note
Action
See
Operating manual - OmniCore
.
Try resetting the FlexPendant using the reset
button located next to the USB port.
1
If it is not connected, repair the
connection and go to step six.
Check that the FlexPendant cable is correctly
connected to the controller through the HMI signal
connector, X4.
2
Check the pins in the connector.
If it is ok, go to the next step.
For more details about the LEDs,
see
Troubleshooting the robot sig-
nal exchange proxy on page 555
•
If the LEDs are not green,
see
bot signal exchange proxy
on page 555
•
If they are ok, go to the next
step.
Check the LED PC and LED HMI, they should be
green.
3
•
If damage is found, replace
the FlexPendant cable and
go to step six.
•
If it is ok, go to the next
step.
Check the FlexPendant cable for any damage.
4
•
If it is not ok, repair the con-
nection and go to step six.
•
If it is ok, go to the next
step.
Check that the connection from the robot signal
exchange proxy to the HMI signal connector is
ok, K2.X9, 13 - X4.
5
Continues on next page
520
Product manual - OmniCore C30
3HAC060860-001 Revision: P
© Copyright 2019-2022 ABB. All rights reserved.
6 Troubleshooting
6.2.5 Problem starting or connecting the FlexPendant
Continued
Summary of Contents for OmniCore C30
Page 1: ...ROBOTICS Product manual OmniCore C30 ...
Page 562: ...This page is intentionally left blank ...
Page 566: ...This page is intentionally left blank ...
Page 574: ...This page is intentionally left blank ...
Page 604: ......
Page 605: ......