LEDs
The illustration below shows the LEDs on the power supply.
A
xx1800000582
DC OK LED
A
Significance
Description
Green: All DC outputs are above the specified minimum levels.
DC OK LED
Off: One or more DC outputs are below the specified minimum level.
Required test equipment
Equipment needed for troubleshooting.
Note
Equipment
Multimeter
Insulating gloves
3HAC059896-009
,
3HAC063898-009
,
3HAC072448-009
Circuit diagram - OmniCore C30
,
Circuit dia-
gram - OmniCore C30 for IRB 14050
,
Circuit
diagram - OmniCore C30 for CRB 15000
Preparations
Action
Check the FlexPendant for errors and warnings.
1
Power the controller off. Wait one minute, power the controller on.
2
Wait 30-60 seconds after power-on.
3
Make sure that the control system power is in run-time mode.
Continues on next page
Product manual - OmniCore C30
551
3HAC060860-001 Revision: P
© Copyright 2019-2022 ABB. All rights reserved.
6 Troubleshooting
6.3.10 Troubleshooting the power supply
Continued