Description
Name
Pin
Reserved
NC
17
Reserved
NC
18
Note
The ESOUT1 and ESOUT2 fulfill the IEC 61131-2 Type 0,25 Output.
Note
The device connected to the ESOUT pins shall fulfill the IEC 61131-2 Type 1
Input.
If the device cannot meet the requirement, a safety PLC or relay is needed.
ESOUT1
-
Safety PLC
or Relay
Relay Output for
Safety Input
of Next Stage
ESOUT2
-
Safety PLC
or Relay
Relay Output for
Safety Input
of Next Stage
Isola!on
Isola!on
K2.X15
Customer provided device
14
13
12
11
xx2000001763
Note
State 0 of Emergency stop output shall be recognized as Emergency stop
triggered.
Note
The maximum length of the cable connected to the ESOUT pins shall be 10 m.
Note
The cable shall be protected from external EM disturbance, suggested to use
separate multicore cables.
Continues on next page
Product manual - OmniCore C30
117
3HAC060860-001 Revision: P
© Copyright 2019-2022 ABB. All rights reserved.
3 Installation and commissioning
3.5.8 Descriptions for connectors
Continued