switching ON and OFF delay:
The output can be switched on or off with
a delay via this function.
•
Flashing:
The output starts to flash as soon as the parameterised value
is received in the communication object
Switch
. The flashing period can
be adjusted via the parameterised time duration for ON or OFF. At the
start of the flashing period the output is switched on with a normally
open contact and off with a normally closed contact. When a new value
is received on the communication object
Switch
the flashing period will
recommence.
The relay state after flashing can be programmed.
Flashing can be inverted when the output is used as a normally closed
contact.
The communication object
Status switch
indicates the current relay state
during flashing.
The following parameter appears with the selection
Flashing
:
Flashing if communication object
"Switching" is
Options: ON
(1)
OFF
(0)
ON (1) or OFF (0)
Here you set the value of the communication object
Switch
at which the
output flashes. Flashing is not retriggerable.
•
ON (1):
Flashing starts when a telegram with the value 1 is received on
the
Switch
communication object. A telegram with the value 0 ends
flashing.
•
OFF (0):
Flashing starts when a telegram with the value 0 is received on
the
Switch
communication object. A telegram with the value 1 ends
flashing.
•
ON (1) or OFF (0):
A telegram with the value 1 or 0 triggers flashing.
Suspension of flashing is not possible in this case.
Duration for ON in value x 0.1 s
[5…65,535]
Options: 5…10…65,535
This parameter defines how long the output is switched ON during a flashing
period.