![ABB i-bus KNX Room Master Premium RM/S 2.1 Product Manual Download Page 80](http://html.mh-extra.com/html/abb/i-bus-knx-room-master-premium-rm-s-2-1/i-bus-knx-room-master-premium-rm-s-2-1_product-manual_3076080.webp)
ABB i-bus
®
KNX
Commissioning
© 2008 ABB STOTZ-KONTAKT GmbH
78
3.2.4.1.3 Parameter window
A: Output
- Logic
In this parameter window all settings for the function
Enable function logic
are undertaken.
This parameter window is visible if in parameter window
, page 63, the parameter
Enable function logic
has been enabled.
The function
Enable function logic
provides up to two logic objects for each
output, which can be logically linked with the
Switch
communication object.
The logic is re-calculated when an object value is received. Hereby,
the communication object
Logical connection 1
is first of all evaluated with
the communication object
Switch
. The result is then logically linked with the
communication object
Logical connection 2
.
Explanations for the logical function can be found at
,
page 220. Please also observe the
, page 215, from which
the priorities can be seen.
Logical connection 1 active
Options: no
yes
With these parameters the communication object
Logical connection 1
is
enabled.
•
yes:
The following parameters appear: