Commissioning
© 2008 ABB STOTZ-KONTAKT GmbH
84
Enable function time
Options: no
yes
•
yes:
The parameter window -
Time
appears.
•
no:
The parameter window remains disabled and invisible.
After the function time has been enabled, the communication object
Permanent ON
is enabled. The output is switched ON via this
communication object. It remains switched ON until a telegram with the
value 0 is received by the communication object
Permanent ON
.
The functions continue to operate in the background during the Permanent
ON phase. The contact position at the end of the Permanent ON phase
results from the functions operating in the background.
Note
All other descriptions of the parameter can be found in parameter window
page 63.